Approved W/ Condition
Approved W/Condition:
1- Maintain horizontal and vertical fire separation between units. Renovated Walls and floors shall Comply with 2018 IBC, 420.2, 708, 711.
2- Provide smoke detector and carbon monoxide detector, comply with 2018 IBC, SECTION907. FIRE ALARM AND DETECTION SYSTEMS and SECTION 915, CARBON MONOXIDE DETECTIO.
3- Indicate designated egress windows at all sleeping rooms, comply with 2018 IBC, SECTION1030 EMERGENCY ESCAPE AND RESCUE.
4- IF existing windows or door will be replaced or not, If existing windows and door is to be replaced, comply with comply with 2018 NFPA 8.3.4.2 (Exterior fire rated doors)
Applied | | 05/29/2024