4/3/2024 -- CORRECTIONS REQUIRED โ The designer needs to clearly indicate his chosen design and the documentation needs to clearly show how the requirements of each option are being applied in each portion of the building. If separated occupancies option, occupancies must be separated in accordance with Table 508.4. When separation is required, occupancies must be separated completely, both horizontally and vertically, with fire barriers and horizontal assemblies.
If using the Special Provisions 510, again the documentation needs to clearly show the section being utilized and the conditions that must be met (examples could be to utilize 510.4 or 510.7 with each having their own provisions (take note however that section 510.7 is only for โopen parking garagesโ below Group A, I, B, M, or R occupancy).